| July 17, 2007 |
Construction Plan Set |
Sheet 1
This aerial photo shows wetlands (blue) that extend in the lower center of the frame to just outside the
border of the OSP site (shown below). The wetlands lead directly to Sequoit Creek to the West of this view.
Sheet 1 Notes
Sheet 1 Legend
Sheet 3
This shows the plan for the OSP, with a large detention area in the SW corner. In the extreme SW corner is a
sedimentation pond, located in the 100' buffer called for in the WDO. Any failure of this pond will impact the
wetlands, and the Creek.
Sheet 3, Detention Pond
Sheet 3, Wetlands
Sheet 3, Notes
Sheet 5
Sheet 6
Sheet 9
Sheet 9, Grading Notes
Sheet 12
The notes on sheet 12 call for 6" of pulverized topsoil, but most of the detention areas, where grass has
not grown, have none.
Sheet 13: Engineered Stormwater Structures
Proper construction of a filtered perforated riser is shown, but the OSP risers are not stabilized to remain
erect. The plans do not show the use of plywood and hay to block a 30" pipe leading to the wetlands.
Sheet 14: Engineered Stormwater Structures |
|
|
March -April, 2008
|
This site was graded before the sediment control ponds were stabilized. Other villages require
run-off to be shunted to temporary sediment ponds while the permanent one are built and stabilized. These reports
show that Antioch not only pursued a plan without these safeguards, but did nothing when the crucial sediment
filters were in disrepair and dysfunctional. SMC also failed their supervisory role, both by not insisting on a
system that would not fail, like this one did last August, and by not taking independent action to protect Sequoit
Creek from illicit discharges in May and June this year.
|
The perforated riser in the sediment pond was compromised for a month,
from 3/6/08 until 4/3/08, despite repeated instructions to correct it. The one in the main detention pond was
compromised for weeks, from 3/20/08 until 4/3/08. This photo also shows the use of plywood and hay to block a 30"
pipe leading to the wetlands.
Erosion and Sediment
Control Report
From Mark Cobb, Engineer, GHA
Dated March 6
Shows compromised sediment filter. However, the Perforated Riser Observations in the report say it’s
installed and mortared in, with adequate stone at the base – all untrue. This report also notes that the detention
and sediment basins are covered with snow and ice – which would mostly melt by the next report. Also shows plywood
used to block exit of sedimentation pond.
Erosion and Sediment
Control Report
From Gewalt Hamilton Associates.
Ron Nissen, Senior Technician, DECI
Dated March 20
Filed May 22, 2008.
Shows that most of the snow and ice did melt, and that it (and any rainwater) bypassed the filter on the
compromised riser, exiting instead through the grill atop the fallen riser, sitting on the ground. All the blanks
in the report’s Perforated Riser Observations indicate no problems with these filters, but the Comments say that
two of them must be re-set.
Erosion and Sediment
Control Report
From Gewalt Hamilton Associates.
Ron Nissen, Senior Technician, DECI
Dated April 3
Filed May 22, 2008.
Shows that the riser in the sediment pond still is not re-set, and that the one in the detention pond is stripped
and out of position. The comments in the report support this, but only one check box indicating a problem is
marked.
Erosion and Sediment
Control Report
From Gewalt Hamilton Associates.
Ron Nissen, Senior Technician, DECI
Dated April 12
Filed May 22, 2008.
Shows that the perforated filtered risers are finally properly installed, but the one in the main pond is already
holding back a lot of water, and the water in the sedimentation pond, presumably getting through the detention
pond filter, is muddy.
|
|
|
May 2, 2008
|
These reports give a conflicted and troubling account. They reveal an April 15 decision to remove
sediment control from the main basin and rely on the sediment basin alone, but the April 3 report shows the filter
removed before this decision was made. After a resident complaint of sediment
in Sequoit Creek on May 2, the sedimentation pond was found unplugged, empty and unstabilized. Nevertheless, these
reports following that declare that the stormwater system, sedimentation basin and inlet protection are "satisfactory,"
and that the adjacent wetlands are protected.
|
Field Observation Report
From Mike Shrake, DECI, GHA
Dated May 2, 3:30 p.m.
Created May 6, 9:31 a.m.
Complaint received May 2, 1:30 p.m.
Plywood blocking exit of only sedimentation control "fallen down."
No discharge from empty pond.
Items marked "N/A":
• Dewatering Facility,
• Restrictor
Items marked "Satisfactory":
• Stormwater System,
• Detention/Sediment Basin Condition
• Inlet Protection
Erosion and Sediment
Control Report
From Gewalt Hamilton Associates.
Dated May 2
Filed May 22, 2008.
Perforated riser filter in sedimentation pond bypassed by open 30" pipe.
Sedimentation basin not stabilized.
Are appropriate dewatering BMP's in place and functioning properly?: "N/A"
Are all adjacent offsite wetlands protected from impact?: "Yes"
Osmond Sports Complex
Memo
From Gewalt Hamilton Associates
Sent May 6
To Tim Cook, SMC
April 15 site meeting agreement to remove perforated riser filter from main basin, and rely on perforated riser filter
in downstream sedimentation pond.
Sedimentation pond empty.
Plywood removal from 30" pipe exiting sedimentation pond a mystery.
DK Contractors waiting for site to dry. Landscape Concepts waiting to apply topsoil, JF New waiting to install native
plant plugs.
Same photographs as May 22 report.
Erosion and Sediment
Control Report
From Gewalt Hamilton Associates.
Ron Nissen, Senior Technician, DECI
Dated April 3
Filed May 22, 2008.
Shows the perforated riser filter damaged or removed from the main detention pond before the April 15 site
meeting.
Main detention pond empty.
Sedimentation pond empty.
Filtered riser in the detention pond compromised, allowing sediment discharge.
Perforated Riser notes contradictory.
|
|